Dashboard components
DC load disconnectors Q1, Q2, Q3 and Q4:4 pcs.
Double pole DC disconnectors.
One disconnector for each string.
They disconnect at the same timeplus and minusof the corresponding string.
Operating voltage: up to1000 V DC.
DC Surge Protection SPD Type 2:4 pcs.
Model in the photo:VCX-PV30
Protection Type:PV T2 / SPD type 2
Maximum operating voltage Ucpv between + and –:1000 V DC
Ucpv between pole and PE:750 V DC
Rated discharge current In:20 kA
Total discharge current Itotal:40 kA
Protection level Up to PE:≤ 3.75 kV
Protection level Up between + and –:≤ 4.75 kV
Degree of protection of the module:IP20
Standard:EN 61643-31
Indication: green / red indicator
Marking:RED = REPLACE
DC Fuse Basics:8 pcs.
Two holders for each thong — for+ and –pole.
Operating voltage: up to1000 V DC.
DC Fuses:8 pcs.
Two fuses per string.
Rated string current:16 A
Overload and short circuit protection.
MC4 Inputs:8 pcs.
For 4 thongs:+ IN1 / – IN1, + IN2 / – IN2, + IN3 / – IN3, + IN4 / – IN4.
DC outputs to inverter:8 pcs.
For 4 thongs:+ OUT1 / – OUT1, + OUT2 / – OUT2, + OUT3 / – OUT3, + OUT4 / – OUT4.
PE ground bus:1 pc.
For protective earthing and connection of the SPD protection.
Internal DC wiring:included.
Wiring between the MC4 inputs, fuses, SPD protection, disconnectors and outputs is factory done.
Cables are sized for16 A per stringand to1000 V DC.
Important
We inform you that, despite our efforts, we cannot guarantee that the published information and photos do not contain inaccuracies or errors that cannot be a legal basis for claims
Technical characteristics
Electrical DC switchboard for protection, disconnection and connection of4 photovoltaic stringsto inverter.
- Purpose:photovoltaic system
- Number of Strings: 4
- Number of DC inputs:4 thongs
- Rated voltage: 1000 V DC
- Rated string current: 16 A
- Total maximum panel current: 63 A
- Degree of protection of the housing: IP66
- Installation:external
- Operating temperature:-25°C to +60°C
- Body:fiberglass reinforced polyester, SMC
- Casing Standard: IEC 62208:2011
Additional information
| color | Gray |
| Number of strings | 4 |
| Tension | up to 1000 V |
| Current | 48 A |