- DC panel for photovoltaic system - 3 strings DC panel for photovoltaic system - 3 strings
DC panel for photovoltaic system - 3 strings
- Description
- Shipping & Returns
- Reviews
Dashboard components
DC load disconnectors Q1, Q2 and Q3:3 pcs.
Double pole disconnectors for direct current.
One disconnector for each string.
They disconnect at the same timeplus and minusof the corresponding string.
Operating voltage: up to1000 V DC.
DC Surge Protection SPD Type 2:3 pcs.
Model in the photo:VCX-PV30
Protection Type:PV T2 / SPD type 2
Maximum operating voltage Ucpv between + and –:1000 V DC
Ucpv between pole and PE:750 V DC
Rated discharge current In:20 kA
Total discharge current Itotal:40 kA
Protection level Up to PE:≤ 3.75 kV
Protection level Up between + and –:≤ 4.75 kV
Degree of protection of the module:IP20
Standard:EN 61643-31
Status indication:green / red indicator
Marking:RED = REPLACE
DC Fuse Basics:6 pcs.
Two pieces of each thong.
One holder for positive and one for negative pole.
Operating voltage: up to1000 V DC.
DC Fuses:6 pcs.
Two fuses per string —+ and –.
Rated string current:16 A
Purpose: overload and short circuit protection.
MC4 Inputs:6 pcs.
For 3 strings:+ IN1 / – IN1, + IN2 / – IN2, + IN3 / – IN3.
Purpose: input from the photovoltaic panels to the switchboard.
DC outputs to inverter:6 pcs.
For 3 strings:+ OUT1 / – OUT1, + OUT2 / – OUT2, + OUT3 / – OUT3.
Purpose: output of the protected DC lines to the inverter.
PE ground bus:1 pc.
To connect the protective earth and SPD protection.
Internal DC wiring:included.
All DC connections between inputs, fuses, SPD protection, disconnectors and outputs are factory made.
Cables are sized for16 A per stringand to1000 V DC.
Important
We inform you that, despite our efforts, we cannot guarantee that the published information and photos do not contain inaccuracies or errors that cannot be a legal basis for claims
Technical characteristics
DC panel to protect and disconnect three PV strings before the inverter.
- Purpose:photovoltaic system
- Number of Strings: 3
- Number of DC inputs:3 thongs
- Rated voltage: 1000 V DC
- Rated string current: 16 A
- Total maximum panel current: 48 A
- Degree of protection of the housing: IP66
- Installation:external
- Operating temperature:-25°C to +60°C
- Body:fiberglass reinforced polyester, SMC
- Casing Standard: IEC 62208:2011
Additional information
| color | Gray |
| Number of strings | 3 |
| Tension | up to 1000V |
| Current | 48 A |